Appendix B. Vendor Information 
Appendix B.1. Echelon LonMaker 
Appendix B.1.1. 
Using LonMaker to comm ission the FieldServer   
 
Ensure  that  the  correct  firmware  and  latest  configuration  is  loaded  on  the  FieldServer  (Each  change  in  the 
FieldServer requires re-commissioning of the FieldServer in LonMaker) 
 
Ensure that the FieldServer and the LonMaker machine are on the same network. 
 
Open the existing Network in LonMaker, or create a new Network 
 
Click on “Create New Network” and follow the network wizard, making the following selections: 
 
Network Interface: Choose Network Attached 
 
Management Mode: Choose Onnet unless you are working offline 
 
Register Plug-ins required. None 
 
Once Visio is open with the Network showing, drag a new device onto the drawing from the toolbox. 
 
Follow the Device Network, making the following selections 
 
Enter Device Name: Choose commission device 
 
Specify Device Template: Choose upload from device 
 
Specify Device Channel: Choose Auto Detect 
 
Specify Device Properties: Leave as is (Ping is optional) 
 
Identify Device: Choose service pin 
 
Device Application Image: Leave unchecked 
 
Initial State: Leave as is 
 
Press the service pin on the FieldServer when asked to do so, and the FieldServer will be commissioned. 
 
Drag a new function block onto the drawing from the toolbox. Give the function block a name and ensure that 
it is allocated to the FieldServer device. 
 
Once the function block is on the drawing, drag input and output variables onto the function block.  LonMaker 
will display the variables available for binding. Click on the variables you require (or use the select all option), 
and they will be commissioned onto the function block. 
 
Connect  these  variables  to  other  devices  by  dragging  connections  from  the  toolbox  and  connecting  the 
variables. 
 
Appendix B.1.2. 
Rem oving Previous FieldServer Device Tem plates in LonMaker.  
If  you  have  previously  used  LonMaker  to  commission  a  FieldServer  or  ProtoCessor  onto  a  LonWorks  network, 
LonMaker saves the properties of that device as a device template.  It is important to remove all previous device 
templates from LonMaker when moving onto your next FieldServer product as some parameters might transfer to 
your new device.   
To  remove  the  device  templates,  open  your  LonMaker  workspace  as  you  would  normally  do.    Then  choose  the 
LonMaker  toolbar  and  choose  the  Device  Templates  option.    This  will  bring  up  a  list  of  all  device  templates.  
Highlight and then remove all device templates that do not contain “Echelon” or “LNS”.  This will ensure a fresh 
commission of your FieldServer product.