Appendix C.4. “Illegal” Characters in Network Variable Names  
Spaces 
Spaces may not be used in Network Variable Names.  The driver automatically replaces all spaces with 
underscores at start-up. 
Brackets   Lonmaker truncates a name from where a bracket is used.  e.g. a name like nviTest[1]Input shows as 
nviTest .  Brackets are therefore not able to be used in Network Variable Names. 
 
Appendix C.5. Circon_SI Limitations 
 
Circon_SI does not recognize whitespace; %; - 
 
The maximum number of Network Variables under Circon_SI is limited to 255 per node. 
Set the Connection_Type parameter in the configuration file  per the following example.   This will ensure that all 
illegal characters are replaced with underscores, and that the number of Network Variables per Node is limited to 
255 in the configuration. 
Example 
//    Client Side Connections 
 
 
 
Connections   
 
Adapter 
,Protocol 
,Connection_Type 
LonWorks 
,LonWorks  ,Circon_SI 
 
Appendix C.6.  Service types currently supported for network variable messages  
Currently  the  service  type  for  network  variable  update  messages  is  fixed  to  acknowledged  service.    Request-
response service is used for network variable poll and network management fetch messages. 
Appendix C.7. Combining Explicit and Implicit  
To  ensure  undisturbed  communication  between  the  network  management  tool  and  the  FieldServer  during  the 
commissioning,  binding  or  monitoring  processes,  the  timeouts  of  the  explicitly  addressed  variables  (Map 
Descriptors) might need to be set to values lower than the message timeouts used by the network management 
tool (LonMaker for Windows).  
LonWorks FieldServer Performance 
No  Desciption 
Min  Typ  Max  Units 
FieldServer startup time with 4096 network variables 
6.5 
Minutes 
Time to commission FieldServer with 4096 network variables 
40 
Minutes 
Time  to  complete  a  network  variable  updFieldServersbetween  two 
FieldServers (acknowledged service) 
40 
Milli-
seconds 
Time  to  complete  a  networFieldServersoll  message  between  two 
FieldServers (request/response service) 
125  - 
Milli-
seconds 
Time  to  complete  a  network  manageFieldServers  variable  fetch  message 
between two FieldServers (request/response service) 
125  - 
Milli-
seconds