DESCRIPTION  
The LonWorks driver allows the FieldServer to transfer data to and from devices using LonWorks protocol.  The FieldServer 
can emulate either a Server or Client.  The FS-B4011 FieldServer is supplied with a LonWorks Card, while the FS-B2011 and FS-
B30 Series FieldServers have a built-in LonWorks Interface.  A Fieldbus connection is available on the FieldServer.  The FS-B30 
and FS-B4011 can handle up to 4096 Network Variables and the FS-B2011 up to 1000 which can be of the Standard Network 
Variable Types (SNVT) and/or User-defined Network Variable Types (UNVT). 
DEFINITIONS 
2.1 
NV Updates/Polls 
On LonWorks networks, information is transferred using Network Variable Updates and Network Variable Polls.  The Client 
requests Network Variables from the Server using Network Variable Polls and Network Variable Updates occur when a Client 
sends Network Variables to a Server. 
2.2 
Network Management 
The  FieldServer  is  able  to  set  its  own  Domain,  Subnet  and  Node  ID  at  start-up  using  the  FieldServer  configuration  file.  
Alternatively,  the  FieldServer  is  capable  of  being  commissioned  and  bound  by  Network  Management  Tools  such  as 
LonMaker® - see Appendix B.1.1 for further information. 
2.2.1  LonWorks - Program ID Calculation (SPID)  
Network management tools use the Program ID to identify the different applications running on each device. Two devices on 
a network may have the same Program ID only if they have identical application/configurations  
The Program ID for the FieldServer consists of a fixed and a variable field (XX in the Program ID below)..  
90:00:95:47:1E:02:04:XX 
The fixed part does not change for different configuration files or for different LonWorks driver versions.  The variable part 
XX, which is also defined as the Model or Revision number, does however change. 
The  variable part  is calculated at start-up  when the  configuration is loaded on the FieldServer.  Certain  critical  fields in the 
configuration file are used to calculate this variable part of the Program ID. Thus if the configuration file changes significantly 
(critical fields) the Program ID will change. Also, as we add new features and capabilities to the LonWorks driver, this variable 
part of the Program ID may be different between LonWorks driver versions (even though the configuration file is the same).  
It  is  possible  though  very  unlikely  that  through  a  change  in  LonWorks  driver  and/or  configuration  file,  the  program  IDs 
calculates out identical to another combination of driver and configuration.  If this is the case with two FieldServers on the 
same network that run different configurations, one of these devices may fail to commission properly. 
The following configuration can be used to force the SPID. 
Connections   
 
Adapter   
,Protocol  
,SPID 
Lonworks  
,Lonworks   ,80:00:95:48:50:02:04:01