FieldServer FS-8700-21 用户手册

下载
页码 62
FS-8700-21 LonWorks Manual 
 
 
 
 
 
 
 
Page 7 of 62 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
HARDWARE CONNECTIONS 
LonWorks  devices  are  available  with  several  different  physical  interfaces.  The  screw  plug  supplied  with  the  FieldServer 
LonWorks interface will connect the FieldServer to the FTT-10 network.  The 9 pin D-connector can also be used to connect to 
the network (FS-B4011 only). The 2-wire twisted-pair connection to the network is polarity insensitive.  The FTT-10 network is 
a free topology network which supports star, loop and/or bus wiring connections.  Please refer to the FTT-10A Free Topology 
Transceiver User’s Guide from Echelon Corporation for recommended wiring practices if necessary.  The connection diagram 
below shows how the FieldServer FS-B2011, FS-B30 and   FS-B4011 are connected to a LonWorks network: 
   FS-X40
FS-X20 
or 
FS-X30
To other 
LonWorks 
Nodes
To other 
LonWorks 
Nodes
FieldBus 
Connector
Pin 1
Pin 2
DB 9 Connector
FieldBus 
Connector
To other 
LonWorks 
Nodes
To other 
LonWorks 
Nodes
 
Configure the remote LonWorks devices according to manufacturer’s instructions.  
4.1 
Service Pin 
The service pin is used to commission the FieldServer onto the network using a LonWorks Network Management tool.  On FS-
B2011 and FS-B4011 FieldServers the node’s unique Neuron ID will be displayed on the Error Screen of the Ruinet utility with 
every service pin press.