FieldServer FS-8700-23 用户手册
FS-8700-23 Cleaver Brooks Hawk Driver Manual
Page 8 of 13
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
4.4.
Client Side Node Descriptors
Section Title
Nodes
Column Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for node
Up to 32 alphanumeric characters
CB Link_ID
Device address
See Section 4.4.1 A, B, and C
below
below
Protocol
Specify protocol used
CB_Link
Port
Port connection
R1-R2
Node_Type
Specify controller connected to CB-
Link
Link
See Section 4.4.2
Example
// Client Side Nodes
Nodes
Node_Name,
CBlink_ID,
Protocol,
Port,
Node_Type
CBH1,
0 1 20,
CB_Link,
R2,
Hawk
4.4.1.
Node_ID
Format for declaring node ID is A B C.
A: 0 if only one CB-Link is attached, 8–254 if multiple CB-Links are attached, Default = 0
B: Slot the device is attached to in the PC Link 1-5, default 1
C: Device type (Declare Device Type Code):
B: Slot the device is attached to in the PC Link 1-5, default 1
C: Device type (Declare Device Type Code):
Device Description
Device Type Code
Auxenh
26
Ec78xx
32
Efenh
26
Hawk
20
Llenh
26
Orenh
26
Pulsa
19
Q7700
1
Qm40xx
17
Rm78xx
32
S7800
36
S7830
34
Tdenh
26
Testcard
99
Trapscan
18
4.4.2.
Node_Type
Hawk, EC78XX. Others by request. (Refer to Device Information Table)