GE 2300 V 用户手册

下载
页码 266
GEH-6385  Reference and Troubleshooting, 2300 V Drives
Chapter 4  Wizards  
••••
  4-27
Drive Commissioning: Current Limits
Enter the normal (1) and alternate (2) per-unit current limits:
Current limit 1 will be used when Torque lim 2 sel is false.
Current limit 2 will be used when Torque lim 2 sel is true.
Drive Commissioning: Power Dip Ride-Through
Power dip ride-through can allow the drive to recover from a momentary loss of line.
The Power Dip Protection attempts to sustain DC link voltage for a selectable time
interval when a low voltage condition is detected. If the line does not recover before
the time expires, the Power dip trip fault will occur.
Related functions
  Power Dip Protection
Drive Commissioning: Parameter Calculation
A calculation is performed in the drive that sets many additional operating
parameters based on the parameters just entered. At the end of the wizard the
parameters will be uploaded to the tool with the opportunity for review.
Drive Commissioning: Simulator Mode
A Simulator mode is available in the drive. The simulator mode allows the drive to
be “run” while not necessarily attached to a motor or to a process. This can be useful
for system evaluation, troubleshooting, or training. In simulator mode the drive will
behave as if it was turning a motor providing speed, current and voltage feedbacks.
Simulated loads and inertias may be set in the menu under drive simulation
parameters.
Drive Commissioning: Hardware Fault Strings in
Simulator Mode
Two protective hardware circuits must be satisfied to allow cell firing and therefore
allow the drive to run. They are Local fault string and System fault string. These
protective strings can be ignored for the purpose of running the drive in simulator
mode. If they are not ignored, they must be satisfied to make the drive run as a
simulator.
Drive Commissioning: Simulator Mechanical
Configuration
Enter the desired values for the parameters, Simulated inertia and Sim const friction.
These parameters are the minimum required to configure the drive's mechanical
simulator. Other simulator configuration parameters are described in the Simulator
function.
Related functions
  Simulator.