USER’S GUIDE
Switched Rack PDU
86
An 
Access
 option (the 
Settings 
option in the control console) enables (by 
default) or disables SNMP. When SNMP is enabled, the 
Access Control
 
settings allow you to control how each of the four available SNMP channels 
is used.
Syslog
By default, the Rack PDU can send messages to up to four Syslog servers 
whenever System (embedded management card) and Switched Rack PDU 
(Device) events occur. The Syslog servers, which must be specifically 
identified by their IP addresses or domain names, record the events in a log 
that provides a centralized record of events that occur at network devices.
Syslog settings. 
Leave the Syslog settings, except the 
Server IP
 settings, 
set to their defaults unless otherwise specified by the Syslog network or 
system administrator.
See also
This user’s guide does not describe Syslog or its configuration 
values in detail. For more information about Syslog, see 
RFC3164, at 
.
Setting
Definition
General Settings
Syslog
Enables (by default) or disables the Syslog feature. 
Facility
Selects the facility code assigned to the Rack PDU’s Syslog messages 
(
User
, by default).
N
OTE
:
Although several daemon-specific and process-specific 
selections are available, along with eight generic selections, 
User
 is 
the selection that best defines the Syslog messages sent by a Rack 
PDU.