Chapter 2     Installation and Configuration
AT-MIO/AI E Series User Manual
2-4
 National Instruments Corporation
16-bit DMA channels, which correspond to channels 5, 6, and 7 in an 
ISA computer and channels 0, 1, 2, 3, 5, 6, and 7 in an EISA computer.  
These selections are all software configured and do not require you to 
manually change any settings on the board.
Interrupt Channel Selection
The AT E Series boards can increase bus efficiency by using an 
interrupt channel.  You can use an interrupt channel for event 
notification without the use of polling techniques.  AT E Series boards 
can use interrupt channels 3, 4, 5, 7, 10, 11, 12, and 15.  These selections 
are all software configured and do not require you to manually change 
any settings on the board. The following tables provide information 
concerning possible conflicts when configuring your AT E Series 
board.
Table 2-1.     PC AT I/O Address Map  
I/O Address Range (Hex)
Device
100 to 1EF
1F0 to 1F8
IBM PC AT Fixed Disk
200 to 20F
PC and PC AT Game Controller, reserved
210 to 213
PC-DIO-24 – default 
218 to 21F
220 to 23F
Previous generation of AT-MIO boards – default 
240 to 25F
AT-DIO-32F – default 
260 to 27F
Lab-PC/PC+ – default
278 to 28F
AT Parallel Printer Port 2 (LPT2)
279
Reserved for Plug and Play operation
280 to 29F
WD EtherCard+ – default 
2A0 to 2BF
2E2 to 2F7
2F8 to 2FF
PC, AT Serial Port 2 (COM2)