Maintenance Object Repair Procedures 
Page 10-233
CABINET (Cabinet Sensors) 
10
b. Refer to AC-POWER (AC-Power) Maintenance documentation for a 
description of this test.
c. Refer to CARR-POW (Carrier Port Power Unit for AC- and DC-Powered 
Systems) Maintenance documentation for a description of this test.
d. Refer to EMG-XFER (Emergency Transfer) Maintenance documentation 
for a description of this test.
e. Refer to EXT-DEV (External Alarm) Maintenance documentation for a 
description of this test.
f. Refer to RING-GEN (Analog Ring Generator) Maintenance documentation 
for a description of this test. This test shows up in the test sequence only if 
there is a TN768 Tone-Clock circuit pack in the port network being tested.
Cabinet Temperature Query Test [for 
Non-Variable Speed Fans] (#122)
This test queries the Maintenance/Tape Processor in a Standard system PPN, the 
Duplication Interface circuit pack in a PPN for a High or Critical Reliability 
system, or the EPN Maintenance circuit pack in an EPN for the status of the 
cabinet sensors in the cabinet that contains non-variable speed fans.
NOTE:
The descriptions for Error Codes 1 and 2 (FAIL) in the following table are 
reversed for Generic 1 systems that use a TN731B maintenance circuit 
pack . That is, Error Code 1 indicates an "over temperature" problem while 
Error Code 2 indicates and "air flow" problem. If you are servicing a Generic 
1 system, be sure to follow the proper service strategy.
Table 10-71.
TEST #122 Cabinet Temperature Query Test [Non-Variable 
Speed Fans] 
Error 
Code
Test 
Result
Description/ Recommendation
1000
ABORT
System resources required to run this test are not 
available.
1. Retry the command at one-minute intervals a 
maximum of five times.
2. If the test continues to abort, escalate the problem.
Continued on next page