DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-294
CARR-POW (Carrier Port Power Unit) for DC-Powered Systems 
10
Power Unit Query Test (#127)
This test queries the Maintenance/Tape Processor in a Standard system PPN, the 
Duplication Interface circuit pack in a PPN for a High or Critical Reliability 
system, or the EPN Maintenance circuit pack in an EPN multicarrier cabinet 
system for the status of the pair of port carrier power units in the specified carrier. 
If both port carrier units are on and functioning, the test passes. If both are not on 
and functioning, the test fails.
PASS
Both port carrier power units in the recycled 
carrier were found to be healthy by the 
Maintenance/Tape Processor in Standard system 
PPN, the Duplication Interface circuit pack in a 
PPN for a High or Critical Reliability system, or the 
EPN Maintenance circuit pack in an EPN 
multicarrier cabinet system after the port carrier 
power units were powered-down and powered up 
again. If the status LEDs on both port carrier 
power units are not showing green, then the 
PR-MAINT (Maintenance/Tape Processor), 
DUPINT (Duplication Interface) circuit pack, or the 
EPN MAINT (Maintenance) circuit pack may have 
incorrectly reported the state of the port carrier 
power units. Look for and resolve any alarms on 
these MOs.
Table 10-85.
TEST #127 Power Unit Query Test 
Error 
Code
Test 
Result
Description/ Recommendation
1000
ABORT
System resources required to run this test are not 
available.
2000
ABORT
Response to the test request was not received within the 
allowable time period.
Continued on next page
Table 10-84.
TEST #126 Power Unit Recycle Test  — 
Continued
Error Code
Test 
Result
Description/ Recommendation
Continued on next page