DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-939
MMI-LEV (Multimedia Interface Resource Level) 
10
administration. Similarly, if a MMI circuit pack is removed from service logically 
by failing the Archangel sanity scan test or is removed from service physically by 
removing the circuit pack from the carrier, no error/alarm is raised against either 
the MMI-BD or the MMI-PT maintenance objects. Therefore, if a MMI-LEV 
error/alarm exists, yet no alarms have been raised against MMI-BD or MMI-PT 
maintenance objects, a MMI circuit pack may have been removed from service 
causing the MMI-LEV error/alarm. To resolve a MMI-LEV MAJOR alarm, restore 
the number of MMI ports available for service to be equal to or greater than the 
calculated port capacity.
To determine how many MMI circuit packs are needed for the MMCH feature:
1. Using the 
display system-parameters maintenance
 command, locate 
the number listed in the 
Minimum Maintenance Thresholds
 
(
MMIs
field and record this number.
2. Use the
 list configuration
 
command to verify the number of MMI ports.
3. Compare this number with the value listed in the 
MMI
 field on the 
System-Parameters Maintenance form (number listed in step 1 a minimum 
thresholds number for MMI ports of between 0-128). Each MMI circuit 
pack contains a maximum of 32 ports. If the number in the 
MMIs
 field is 
less than or equal to 32, one MMI circuit pack is needed. If this number is 
64, then two MMI circuit pack are needed.
4. Use the 
list configuration
 command to verify that the number of MMI 
circuit packs listed agrees with the required minimum port capacity (from 
step 1). If the number of MMI circuit packs listed in the step 2 differs from 
the calculated number, restore the number of MMI circuit packs to the 
correct value, in order to resolve the MMI-LEV alarm.
Error Log Entries and Test to Clear Values
To resolve this alarm, correct the out-of-service problem by following these procedures:
1. See “MMI-PT” and “MMI-BD” and resolve any associated alarms.
2. If a MMI-LEV error/alarm exist and none has been raised against MMI-BD or 
MMI-PT maintenance objects, an MMI circuit pack may have been removed from 
service causing the MMI-LEV error/alarm. To resolve a MMI-LEV MAJOR alarm, 
1.
The number of MMI resources in the system that are in service has fallen below the calculated 
minimum value. If the number of in-service MMI ports falls below the MMCH port capacity 
(value entered in the Minimum Maintenance Thresholds for MMIs
 field) on the 
System-Parameters Maintenance form, a MMI-LEV error is logged. If this outage continues for 
15 minutes, a MAJOR alarm is raised. 
Table 10-269.
MMI-LEV Error Log Entries 
Error 
Type
Aux 
Data
Associated Test
Alarm 
Level
On/ Off 
Board
Test to Clear Value
1
1
Any
None
MAJOR
OFF