Lucent Technologies R5SI 用户手册

下载
页码 2643
DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-1326
SYNC (Synchronization) 
10
scenario, is designated the 
master
 port network and the EPNs are called 
slave
 
port networks. The 
master
 port network is defined as the port network that 
contains the system synchronization source. If the primary synchronization 
reference does not provide a valid timing signal, Synchronization Maintenance 
switches to the secondary reference. 
Both the primary and secondary 
references must reside in the same port network, but there is no restriction 
as to in which port network both must reside (that is, both references may 
be in an EPN). The recommended placement of the references is in the PPN.
There are two kinds of Stratum 4 synchronization that are supported: Type I and 
Type II. Stratum 4 type I is more stable than Type II and provides some switching 
capability at the hardware level. Stratum 4 Type II operation is the only 
synchronization strata provided by Generic 1. It is important to note that Stratum 
4 Type I operation is not possible when one or both of the DS1 interface circuit 
packs providing the reference sources is a TN722. Both must be the TN767 or 
TN464 (suffix C or higher).
Stratum 3 Synchronization
The following diagram may help you to understand the synchronization 
components needed for Stratum 3 synchronization.
NOTE:
This is only one possible configuration.