Maintenance Object Repair Procedures
Page 10-1409
TDM-BUS (TDM Bus)
10
Standby Reference Health Check Test (#651)
This test evaluates the quality of the external synchronization timing source for
the Standby Tone-Clock circuit pack.
the Standby Tone-Clock circuit pack.
Table 10-429.
TEST #651 Standby Reference Health Check Test
Error
Code
Code
Test
Result
Description/ Recommendation
ABORT
This test may already be running due to a tone-clock installation, scheduled
maintenance, alarm activity, or a technician-demand test from another
terminal. This abort can also occur due to an internal system error.
maintenance, alarm activity, or a technician-demand test from another
terminal. This abort can also occur due to an internal system error.
1. Try the command again at 1-minute intervals up to five times.
1184
ABORT
This test requires an external synchronization source to be administered
(DS1 primary, DS1 primary and secondary, or Stratum 3 Clock).
(DS1 primary, DS1 primary and secondary, or Stratum 3 Clock).
1. Administer the external synchronization source and retry the test.
2500
ABORT
Internal system error
1. Try the command again at 1-minute intervals up to 5 times.
0
FAIL
If the Tone-Clock circuit pack is in the PPN
, the external synchronization
timing source for side A of the Stratum 3 clock, or for the Primary DS1
reference is either absent or invalid.
reference is either absent or invalid.
If the Tone-Clock circuit pack is in
an EPN
, the synchronization reference from the active EI circuit pack is
either absent or invalid.
1
FAIL
If the Tone-Clock circuit pack is in the PPN
, both external
synchronization timing sources are either absent or invalid.
If the
Tone-Clock circuit pack is in an EPN
, the synchronization references
from both EI circuit packs are either absent or invalid.
1. Correct the synchronization source problem. Refer to the
Synchronization (SYNC) maintenance section of this manual.
2. If the error still exists, replace the Tone-Clock circuit pack reported in
the error log.
PASS
The external synchronization timing source is valid.
Continued on next page