Omron C200HE 用户手册

下载
页码 564
66
Word(s)
Default
Function
Bit(s)
DM 6551
00 to 07
Baud rate
00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K
1.2 K
08 to 15
Frame format
Start
Length
Stop
Parity
00: 
1 bit
7 bits
1 bit
Even
01: 
1 bit
7 bits
1 bit
Odd
02: 
1 bit
7 bits
1 bit
None
03: 
1 bit
7 bits
2 bit
Even
04: 
1 bit
7 bits
2 bit
Odd
05: 
1 bit
7 bits
2 bit
None
06: 
1 bit
8 bits
1 bit
Even
07: 
1 bit
8 bits
1 bit
Odd
08: 
1 bit
8 bits
1 bit
None
09: 
1 bit
8 bits
2 bit
Even
10: 
1 bit
8 bits
2 bit
Odd
11: 
1 bit
8 bits
2 bit
None
1 start bit, 7-bit
data, 1 stop bit,
even parity
DM 6552
00 to 15
Transmission delay 
0000 to 9999: BCD in 10-ms units.
0 ms
DM 6553
00 to 07
Node number (Host Link)
00 to 31 (BCD)
0
08 to 11
Start code enable (RS-232C)
0: Disable; 1: Set
Disabled
12 to 15
End code enable (RS-232C)
0: Disable (number of bytes received)
1: Set (specified end code)
2: CR, LF
Disabled
DM 6554
00 to 07
Start code (RS-232C)
00 to FF (binary)
0000
08 to 15
12 to 15 of DM 6553 set to 0:
Number of bytes received
00: Default setting (256 bytes)
01 to FF: 1 to 255 bytes
12 to 15 of DM 6553 set to 1:
End code (RS-232C)
00 to FF (binary)
Communications Board Port A Settings (DM 6555 to DM 6559)
The following settings are read continually while the PC is ON.
DM 6555
00 to 03
Port settings
0: Standard (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps)
1: Settings in DM 6556
Standard
04 to 07
CTS control setting
0: Disable CTS control
1: Enable CTS control
Disable
08 to 11
Words linked for 1:1 PC Link (Can’t be changed once set in the 1:1 PC Link
Master.)
0: LR 00 to LR 63; 1: LR 00 to LR 31; 2: LR 00 to LR 15
Maximum PT node number for 1:N NT Link
1 to 7 BCD (1 to 3 with a C200HE-CPU
-E
 
PC)
LR 00 to LR 63
12 to 15
Communications mode
0: Host Link; 1: RS-232C; 2: 1-to-1 link slave; 3: 1-to-1 link master;
4: NT Link (1:1); 5: NT Link (1:N); 6: Protocol Macro
Host Link
DM (Data Memory) Area
Section 3-6