Symmetricom 1100 用户手册

下载
页码 224
097-58001-02 Revision G – April 2008
TimeProvider User’s Guide 135
Chapter 4 Provisioning the TimeProvider
Provisioning Alarms
Sample Command
RTRV-COND::IOC:TS1000;
Normal Response
TP-SSU 03-10-24 11:27:28
M
TS1000 COMPLD
“SYS,PWRA-OK,PWRB-OK,OK,OK”
;
Clearing Alarms
Clearing the Office (Audible) Alarm
Use the following TL1 command to turn off (squelch) the audible office alarm. The 
office alarm reactivates when a new alarm occurs.
OPR-ACO-ALL:[<tid>]::[<ctag>];
<aid>
Description
SYS
Displays the connectivity status of the Expansion Panel and any 
alarms associated with the Expansion Panel
<pwra> – PWRA-OK | PWRA-FAIL
<pwrb> – PWRB-OK | PWRB-FAIL
<expstatus> – OK | ALM
<extfault> – OK | ALM
IMC
Displays all conditions related to the Information Management module
<ioc1comm> – IOC1COMM-OK | IOC1COMM-FAIL
<ioc2comm> – IOC2COMM-OK | IOC2COMM-FAIL
IOCm
m = 1 | 2
Displays the current setup and conditions related to the system-level 
function of the IOC module
<iocstatus> – OK | ALM (IOCFAIL)
<ioccomm> – IOC1TO2COMM-OK | IOC1TO2COMM-FAIL 
IOC2TO1COMM-OK | IOC2TO1COMM-FAIL
<imccomm> – IMC1COMM-OK | IMC1COMM-FAIL | 
IMC2COMM-OK | IMC2COMM-FAIL
GPS
Displays GPS Input state and any alarm events associated with GPS 
input
<gpsstatus> – OK | ALM
PRS
Displays PRS Input state and any alarm events associated with PRS 
input
<prsstatus> – OK | ALM
INPp 
p = 1 | 2
Displays Input state and any alarm events associated with Inputs 1 or 2
<inpstatus> – OK | ALM
OUTg 
g = 1 | 2 | 3 | 4
Displays output status; this reflects the state of IOCFAIL of the active 
IOC
<outstatus> – OK | ALM