Baldor MN850 用户手册

下载
页码 70
Section 1
General Information
Applications B-3
MN850
                      
  Read Only Parameter Values
Title
P#
Parameter
Adjustable Range
Factory
User Setting
Parameters
P74
2nd Last Trip
1–16 (Status Code)
0
P75
3rd Last Trip
1–16 (Status Code)
0
P76
4th Last Trip
1–16 (Status Code)
0
P77
5th Last Trip (Oldest trip)
1–16 (Status Code)
0
P78
Protection Mode 2
0–192
192 (Full + Optimize)
P79
Start Pedestal 2
10–60%
50 (% of line volts)
P80
Start Time 2
1–255 seconds
5 seconds
P81
Kick Pedestal 2
60–90%
75 (% of line volts)
P82
Kick Time 2
10–40 seconds
25 seconds
P83
Dwell 2
1–255 seconds
5 seconds
P84
Stop Pedestal 2
10–60 seconds
10 seconds
P85
Stop Time 2
0–255 seconds
0 seconds
P86
Auto Config 2
0–255
6 (Bit 00000110)
P87
Under Current 2
0–1 (x 
I
e) Amps
0.125 x 
I
e Amps
P88
Under Current Time 2
5–255 seconds
50 seconds
P89
Current Limit 2
0–8 (x 
I
e) Amps
4 x 
I
e Amps
P90
Current Limit Time 2
5–255 seconds
15 seconds
P91
Shearpin 2
1–5 (x 
I
e) Amps
3 x 
I
e Amps
P92
Shearpin Time  2
5–255 cycles
50 cycles
P93
Overload Level 2
0.5–2 (x 
I
e) Amps
1.09375 x 
I
e Amps
P94
Overload Delay 2
10–140 seconds
140 seconds
P95
User Flags 1 (for 2nd param set)
0–255
134 (Bit 10000110)
P96
User Flags 2 (for 2nd param set)
0–255
64  (Bit 01000000)
P97
Flag 1 I/P Source Address
0–125
0 (Parameter #)
P98
Flag 1 I/P Source Mask
0–128
0 (bit 00000000)
P99
Flag 1 O/P Destination Address
0–125
0 (Parameter #)
P100
Flag 1 O/P Destination Mask
0–255
0 (bit 00000000)
P101
Flag 2 I/P Source Address
0–125
0 (Parameter #)
P102
Flag 2 I/P Source Mask
0–20
0 (bit 00000000)
P103
Flag 2 O/P Destination Address
0–125
0 (Parameter #)
P104
Flag 2 O/P Destination Mask
0–11
0 (bit 00000000)
P105
Loop Input
0–125
41 (Parameter #)
P106
Loop Feedback
0–125
26 (Parameter #)
P107
Error Gain
1–255
37
P108
Error Divisor
1–255
7
P109
Max Slope
0–50
10
P110
Guard Gap
0–150
10