Receiving & Installation 3-37
MN715
Figure 3-39  Opto-Output Equivalent Circuit
Opto Output 1
Opto Output 2
Opto Out 1 Return
J4
See recommended terminal tightening torques in Section 6.
Opto Out 2 Return
PC865
50mA max
10 - 30VDC
Opto Outputs
PC865
50mA max
18
19
20
41
42
Note: These outputs are programmed in the Level 1, 
Output block, parameters Digital Out #1 and #2.
Relay Outputs
Two programmable relay outputs are available at terminals J4-21 and J4-22.  See Figure
3-40.  Each output can be individually configured as normally open (N.O.) or normally
closed (N.C.) contacts.  Jumpers JP3 and JP4 select the N.O. or N.C. contacts.  These
outputs may be wired as shown in Figure 3-40.
Each output may be programmed to represent one output condition. The output
conditions are defined in Section 4 of this manual.
Figure 3-40  Relay Output Connections
Relay1 Output
Relay2 Output
Relay1 Out Return
J4
See recommended terminal tightening torques in Section 6.
Relay2 Out Return
5 Amperes Maximum
10 - 30VDC  or
230VAC
21
22
43
44
RE
MOV
JP4
Relay2
RE
MOV
JP3
Relay1
Note: These outputs are programmed in the Level 1, 
Output block, parameters Digital Out #3 and #4.