3   GENERAL SPECIFICATIONS 
 
3 GENERAL SPECIFICATIONS 
 
Performance specification of PLC is as follows: 
 
Item Specifications 
Operating ambient 
temperature 
0 to 55°C 
Storage ambient 
temperature 
-25 to 75°C  3 
Operating ambient 
humidity 
5 to 95%RH  4, non-condensing 
Storage ambient 
humidity 
5 to 95%RH  4, non-condensing 
 Frequency 
Acceleration 
Amplitude 
Sweep 
count 
10 to 57Hz 
——— 
0.075mm 
(0.003inch) 
Under 
intermittent 
vibration 
57 to 150Hz 
9.8m/s
2
 
——— 
10 to 57Hz 
——— 
0.035mm 
(0.001inch) 
Vibration resistance 
Conforming 
to  
JIS B 3502, 
IEC 61131-2 
Under 
continuous 
vibration 
57 to 150Hz 
4.9m/s
2
 
——— 
10 times each in 
X, Y, Z directions 
(for 80 min.) 
Shock resistance 
Conforming to JIS B 3502, IEC 61131-2 (147 m/s
2
, 3 times in each of 3 directions X, Y, Z) 
Operating ambience 
No corrosive gases 
Operating altitude 
2000m (6562ft.) max. 
Installation location 
Inside control panel 
Overvoltage 
category  1 
II max. 
Pollution level  2 2 
max. 
 
1 : This indicates the section of the power supply to which the equipment is assumed to be connected 
between the public electrical power distribution network and the machinery within premises. Category II 
applies to equipment for which electrical power is supplied from fixed facilities. 
The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V. 
2 : This index indicates the degree to which conductive material is generated in terms of the environment in 
which the equipment is used. 
Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by 
condensing must be expected occasionally. 
3 : The storage ambient temperature is -20 to 75°C if the system includes the AnS series modules. 
4 : The operating ambient humidity and storage ambient humidity are 10 to 90%RH if the system includes the 
AnS series modules. 
5 : Do not use or store the PLC under pressure higher than the atmospheric pressure of altitude 0m. 
Doing so can cause a malfunction. 
When using the PLC under pressure, please contact your sales representative. 
 
 
 
 
 
 