PMCM-ETHCC-0208 
ACCESS 9340 and 9360 Meter Ethernet Communications Card
2/2008
Setup
© 2008 Siemens Energy & Automation, Inc.. All Rights 
9
EN
G
L
IS
H
Serial Port
Action
Result
1. From the Setup menu, click Serial Port.
Opens the Serial Port page.
2. Select your physical interface, 
transmission mode, baud rate, parity, and 
response timeout (see Table 5 on page 9).
Selects the serial port options.
3. Click Apply.
Updates the 9340-60-ETHER module Serial 
Port settings.
Figure 4:
Serial Port Page
Table 5:
Serial Port Settings
Option
Description
Setting
Physical Interface
Used to select how the 9340-60-ETHER 
module serial port is physically wired.
RS485 4-wire or RS485 2-wire
Default: RS485 2-wire
Transmission 
Mode
Used to select how data is transmitted over 
a serial connection.
Automatic or Modbus ASCII
Default: Automatic
NOTE: Automatic mode allows 
you to communicate to 
Modbus RTU and ACCESS 
slave devices on the same 
daisy chain. These devices are 
entered on the Device List 
page.
Baud Rate
Used to select the data transmission speed 
over a serial connection.
2400, 4800, 9600, 19200, 
38400
Default: 19200
Parity
Used to select if data is checked for 
accuracy using a parity bit.
Even, Odd, None
Default: Even
Response Timeout Used to select how long the 
9340-60-ETHER module will wait to receive 
a response from a serial device.
0.1 to 10 seconds
Default: 3 seconds