There are two communications ports on the Gateway, labeled PLC1 and PLC2.  Each port can be 
configured for either RS232 or RS485 operation.  Gateway can communicate through either the T-Series 
RS232 programming port or the RS485 computer link port.   
 
 
 
 
 
Gateway is setup using simple MS Windows setup software.   The software allows devices/registers from 
one device to be mapped to devices/registers of the other device.  For Modbus, the 400001 numbered 
holding registers can be mapped directly to D data registers in the Toshiba PLC.   
 
 
 
 
 
 
 
In the above example, 5 data registers in the T1 PLC starting at D101 are written into PID controller 
modbus registers starting with holding register 400001.   3 Holding registers in the PID controller are 
written into the data registers of the T1 starting at D0 (D0 –D2).  It is also possible to control the priority 
and frequency of the data transfer using the Gateway setup software. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Page 3 
 
Power Supply: 
24 VDC +/- 5 % (50 ma MAX.) No Fuse inside 
 
5 VDC +/- 5 % FROM PLC  (120 ma MAX.) 
Communication: 
Two ports as follows: 
      
     Com 1: RS232C/RS485 
 
     Com 2: RS232C/RS485  
Status LEDs: 
PLC1 LED 
 STATUS 
LED 
   
PLC2 LED 
Temperature:  
Operating: 0 to 60 
°C     Storage: - 40 to 90 °C 
Humidity: 
10% to 90% (Non condensing) 
Immunity to ESD: 
Level 3 as per IEC1000-4-2  
Immunity to Transients: 
Level 3 as per IEC1000-4-4 
Radiated Susceptibility: 
Level 3 as per IEC1000-4-3 
Emissions: 
EN55011 CISPR A 
Dimensions: 
97mm(W) X 15.mm (H) X 42mm(D)  DIN RAIL mounting 
available 
Weight: 
100 gm Approx. 
 
    
 Gateway Modes 
 Gateway Setup 
 Specifications