Chapter 3
VXI-MXI-2 Configuration and Installation
3-6
ni.com
Figure 3-3.  VXIbus Slot Configuration
When the VXI-MXI-2 is installed in Slot 0, it becomes the VMEbus 
System Controller. In this role, it has VMEbus Data Transfer Bus Arbiter 
circuitry that accepts bus requests on all four VMEbus request levels, 
prioritizes the requests, and grants the bus to the highest priority requester. 
As VMEbus System Controller, the VXI-MXI-2 also drives the 16 MHz 
VMEbus system clock by an onboard 16 MHz oscillator.
As required by the VXIbus specification, the VXI-MXI-2 drives the 
10 MHz signal CLK10 on a differential ECL output when installed in 
Slot 0. When not installed in Slot 0, the VXI-MXI-2 only receives the 
CLK10 signal.
a. Automatic Slot 0 Detection (Default)
b. Manual Slot 0 Configuration
c. Manual Nonslot 0 Configuration
Slot 0
Auto
Nonslot 0
W2
Slot 0
Auto
Nonslot 0
W2
Slot 0
Auto
Nonslot 0
W2