Omron CJ1W-EIP21 用户手册

下载
页码 464
171
Setting Tag Data Links
Section 6-2
If the operating mode of one or more CPU Units was changed to download
the parameters, the CPU Units can be returned to the previous operating
mode. If the No Button is clicked, the CPU Units will remain in PROGRAM
mode. 
4.
The following dialog box will be displayed, indicating that the download was
completed.
6-2-11 Uploading Tag Data Link Parameters
Tag data link parameters (such as the tag set settings and connection set-
tings) can be uploaded from EtherNet/IP Units in the EtherNet/IP network.
The following procedure shows how to upload the parameters. For details on
connecting to the network from the Network Configurator, refer to 6-2-9 Con-
necting the Network Configurator to the Network
.
1,2,3...
1.
Connect the Network Configurator to the network. 
2.
There are two ways to upload the parameters.
• Uploading from All Devices in the Network
Select Network - Upload. The following dialog box will be displayed.
• Clicking the Yes Button:
Parameters will be uploaded only from the devices registered in the Net-
work Configuration Window. Parameters will not be uploaded from devices
that are not registered in the Network Configuration Window.
• Clicking the No Button:
• If parameters are being uploaded from all devices in the network, the
parameters will be newly uploaded from all devices. The current net-
work configuration information will be lost.
• If parameters are being uploaded from specified devices only, the up-
load operation will be cancelled and the upload will not be performed.
• Clicking the Cancel Button:
The upload operation will be cancelled and the upload will not be per-
formed.
• Uploading Individually from Particular Devices