Omron CJ1W-EIP21 用户手册

下载
页码 464
10
Network Configurator Overview
Section 1-5
1-5
Network Configurator Overview
1-5-1
Overview
The Network Configurator Ver. 3.0 or higher is a software package designed
for building, setting, and controlling a multi-vendor EtherNet/IP Network using
OMRON's EtherNet/IP. It is included in CX-One version 4.0 or higher. The
Network Configurator provides the following functions for building, setting, and
controlling EtherNet/IP.
Network Control
The Network configuration can be created and edited regardless of whether
the Network Configurator is online or offline. The Network configuration can
be read from a file or the network.
Hardware (EDS File) 
Control
EDS files used by the Network Configurator can be installed and deleted.
1-5-2
Network Configurator Requirements
Item
Specification
Operating environment
Refer to the CX-One Setup Manual (W463).
CXONE-AL
@@
C-V4/CXONE-AL
@@
D-V4
Network 
connection 
method
CS1/CJ1
CJ2
Serial interface
CPU Unit’s Peripheral or RS-232C port
CPU Unit’s USB or RS-232C port
Ethernet interface
EtherNet/IP Unit’s Ethernet port
CPU Unit’s Ethernet port
EtherNet/IP Unit’s Ethernet port
Location on Network
A single node address is used (only when directly connected to EtherNet/IP).
Number of Units that can be 
connected to Network
A single Network Configurator per network (More than one Configurator cannot be 
used in the same system.)
Main func-
tions
Network control 
functions
• The network configuration can be created and edited regardless of whether the Net-
work Configurator is online or offline.
• The network configuration can be read from a file or the network.
Hardware control
functions
The EDS files used by the Network Configurator can be installed and deleted.
Supported file formats
Configurator network configuration files (*.nvf)
Configuration files (*.ncf) created using the Network Configurator for EtherNet/IP 
(version 2) can be imported by selecting External Data - Import from the File 
Menu.