14-4-4 Error Log Error Codes
Error 
code 
(hex)
Error
Detail code
Saved in 
EEPROM
First byte
Second byte
0001
CPU Unit watchdog timer error
00 hex
00 hex
Yes
0002
CPU Unit service monitoring error 
Monitoring time (ms)
Yes
0006
Other CPU error
Bit D11: Unit not in Registered I/O Tables
(Other bits are reserved for system use.)
Yes
000E
I/O bus error
00 hex
00 hex
Yes
000F
CPU Unit initialization error
00 hex
00 hex
Yes
0011
Event timed out
MRC (main command)
SRC (subcommand)
Yes
0012
CPU Unit memory error
01 hex: Read error
02 hex: Write error
03 hex: Routing tables
50 hex: CPU Bus Unit 
Area (CIO or DM)
Yes
0015
CPU Unit fatal error
00 hex
00 hex
Yes
0017
Tag database error
00 hex
00 hex
Yes
0103
Resend count exceeded (send failed)
FINS Command:
Bit 15: OFF
Bits 08 to 14: Source network address
Bits 00 to 07: Source node address
FINS Response:
Bit 15: ON
Bits 08 to 14: Destination network address
Bits 00 to 07: Destination node address
CIP Frame:
FFFF
No
0105
Node address setting error (send failed)
No
0107
Remote node not in network (send failed)
No
0108
No Unit with specified unit address (send 
failed)
No
010B
CPU Unit error (send failed)
No
010D
Destination address not in routing tables 
(send failed)
No
010E
Not registered in routing tables (send failed)
No
010F
Routing table error (send failed)
No
0110
Too many relay points (send failed)
No
0111
Command too long (send failed)
No
0112
Header error (send failed)
No
0117
Internal buffers full; packet discarded
No
0118
Illegal packet discarded
No
0119
Local node busy (send failed)
No
0120
Unexpected routing error
No
0122
Service not supported in current mode; 
packet discarded
No
0123
Internal send buffer full; packet discarded
No
0124
Maximum frame size exceeded; routing 
failed
No
0125
Response timeout; packet discarded
No
020F
Communications controller error
00 hex
01 hex
Yes
0211
IP address duplication
Port number (always 02)
Lower byte of IP address
Yes
021A
Logic error in setting table
00 hex
02 hex: Network parame-
ters
03 hex: Routing tables
04 hex: Unit Setup
0E hex: Unit name
12 hex: Status area layout 
setting error
13 hex: Status area layout 
setting verification error
15 hex: Installation in a 
PLC of another series 
(e.g., from CJ1 to CJ2) 
after setting the Unit.
Yes