Troubleshooting
Section 14-5
Note
If a memory error occurs in the error log area of EEPROM, the record will not
be stored in EEPROM.
14-5 Troubleshooting
14-5-1 CPU Unit's ERR/ALM Indicator Lit or Flashing
Use the following table to troubleshoot the system when the CPU Unit’s ERR/
ALM indicator is lit or flashing when the EtherNet/IP Unit or built-in EtherNet/
IP port is mounted.
For details, refer to the CPU Unit’s Operation Manual.
03D3
Link OFF error
00 hex
00 hex
No
03D4
Verification error (Tag data link only)
Note For details on identifying the cause of 
the verification error, refer to 14-3 
Connection Status Codes and Error 
Processing
.
This error will not be stored when a 
target node is missing for version 2.0 
or higher.
Connection instance num-
ber (0 to 255)
Lower byte of IP address
No
03D5
Tag data link error
00 hex
Lower byte of IP address
No
0601
CPU Bus Unit error
Variable
Yes
0602
CPU Bus Unit memory error
01: Read error
02: Write error
02 hex: Network parame-
ter
06 hex: Error log
09 hex: Identity data
0E hex: Unit name
0F hex: Ethernet basic 
setting
10 hex: Ethernet 
advanced setting
11 hex: MAC address
12 hex: Status area layout 
setting
14 hex: Term Tag address 
resolution memory write 
error 
Yes 
(See 
note.)
Error 
code 
(hex)
Error
Detail code
Saved in 
EEPROM
First byte
Second byte
An I/O verification 
error occurred.
• Confirm that the Unit is connected properly.
• Check the I/O table with the I/O Table Verification operation 
and correct it if necessary. After correcting it, perform the I/O 
Table Create operation.
A CPU Bus Unit 
setting error 
occurred.
• The CPU Bus Unit model registered in the I/O tables does 
not match the model of CPU Bus Unit actually mounted. 
Check the I/O tables with the I/O Table Verification operation 
and correct it if necessary.
After correcting the I/O tables, perform the I/O Table Create 
operation.
A CPU Bus error 
occurred.
• Confirm that the Unit is connected properly.
• Restart the Unit. Replace the Unit if it doesn’t restart.
An I/O Bus error 
occurred.
• Confirm that the Unit is connected properly.
• Restart the Unit. Replace the Unit if it doesn’t restart.