Omron CJ1W-EIP21 用户手册

下载
页码 464
15
EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications
Section 2-1
CJ-series EtherNet/IP Unit
Note
If tag data links are being used, use 100Base-TX. Otherwise, 10Base-T can
be used, but this is not recommended.
Item
Specifications
Model number
CJ1W-EIP21
Type
100Base-TX (See note.)
Applicable PLCs
CJ-series PLCs
Unit classification
CJ-series CPU Bus Unit
Mounting location
CPU Rack or Expansion Rack
Number of Units that can be 
mounted
8 max. (including Expansion Racks)
Note Up to seven EtherNet/IP Units can be connected to a CJ2H-CPU
@@
-EIP CPU 
Unit. Up to two EtherNet/IP Units can be connected to a CJ2M CPU Unit.
CPU Unit 
words used
Allocated CIO Area 
words (CPU Bus 
Unit words)
25 words/Unit (one unit number’s words)
These words contain control bits and flags, the target node PLC’s operating and error 
information, Unit status, communications status, registered/normal target node infor-
mation, and FINS/TCP connection status.
Allocated DM Area 
words (CPU Bus 
Unit words)
100 words/Unit (one unit number’s words)
These words contain the IP address display/setting area.
User-set area
Any usable data area words
Target node PLC’s operating and error information, and registered/normal target 
node information
CPU Bus Unit Sys-
tem Setup
Not used.
Non-volatile memory within Ether-
Net/IP Unit (See note.)
The following settings are stored in the EtherNet/IP Unit’s non-volatile memory.
Note Unlike the regular Ethernet Units, the CPU Bus Unit Setup Area in the CPU 
Unit is not used for these settings.
1. Unit Setup (communications settings for the EtherNet/IP Unit, such as the IP ad-
dress, DNS server settings, host name, baud rate, FINS/UDP settings, and FINS/
TCP settings)
2. Tag data link settings (device parameters)
Transfer 
specifica-
tions
Media access 
method
CSMA/CD
Modulation method
Baseband
Transmission paths
Star form
Baud rate
100 Mbit/s (100Base-TX)
Transmission media
Shielded twisted-pair (STP) cable
Categories: 100 
Ω
 at 5, 5e
Transmission dis-
tance
100 m (distance between hub and node)
Number of cascade 
connections
There is no limitation when a switching hub is used.
Current consumption (Unit)
410 mA max. at 5 V DC
Weight
94 g max.
Dimensions
31 
×
 90 
×
 65 mm (W 
×
 H 
×
 D)
Other general specifications
Other specifications conform to the general specifications of the CJ-series.