Omron CJ1W-EIP21 用户手册

下载
页码 464
59
Tag Data Link Parameters
Section 3-9
3.
Select Datalink 
 Wizard from the menus in the Datalink Tool when it has
started. 
4.
In the Datalink Wizard Dialog Box, enter 50 words starting from memory
address W000 for area 1 and 100 words starting from D00050 for area 2,
and then press the OK Button.
5.
The data link settings will be automatically created in the window of the
EtherNet/IP Datalink Tool. Select File 
 Save to end. The settings will be
saved in the Network Configurator.