GE GFK-1541B 用户手册

下载
页码 240
GFK-1541B
Chapter 2  Installation
2-27
2
 
States of the Series 90-30 CPU364 with Embedded TCP/IP Ethernet Interface
Ethernet Interface
Initializing
(approx. 2-6 seconds)



The Ethernet Interface is initialized by
- Powering-up the PLC
- Storing a new configuration to the PLC with changes for the Ethernet Interface
- Pressing the Restart pushbutton
- Issuing a Station Manager   RESTARTLOAD, or MAINT command
- Internal System Error occurring when Interface is Operational
Diagnostics
Pass?
Load
Request or
Software
Corrupted?
Waiting for
Configuration
from PLC CPU
(max. 2 seconds)
C
œ


IP address =
 0.0.0.0
Maintenance
Request or
Fatal System
Error?
Operational
Software Load Caused by
- Restart pushbutton pushed until bottom LED turns ON
- Station Manager  LOAD command issued
- Detection of corrupt software
Waiting for IP Address Caused by
- Not configuring Interface using configuration software
- Configuring Interface with IP address = 0.0.0.0
- New CPU with no configuration
- CPU failure to communicate with Interface
Continue to Maintenance or Operational Caused by
- IP address received from network BOOTP server
- IP address entered by   BOOTP  Station Manager command
Maintenance Request Caused by
- Restart pushbutton pushed until bottom two LEDs turn ON
- Station Manager   MAINT command issued
- Fatal System Error while in Operational State forced a restart
The LEDs are labeled from top to bottom as follows:
EOK
LAN
STAT
The symbols used for the LEDs are defined as follows:
 

 
= OFF
 
z
  = ON
 
œ
 = Slow Blink; multiple slow blinking LEDs blink in unison
 

 = Fast Blink
  
   = Traffic (blinks when there is traffic on the line)
The process symbols are defined as follows:
           = Temporary condition; requires no intervention
           =  Decision point during power-up
           =  Interface State; normally the Interface remains
                in a State unless there is user intervention
Symbols 
z
z
/

z
/

F
Hardware
A
Failure



Software
B
Load
œ
œ
œ
Waiting for
D
œ
z
/

œ
IP Address
Maintenance
z
/

z
/

E
No
No
No
No
Yes
5
Yes
3
Yes
2
Yes
Done
IP Address
Received
4
Maintenance
- Client and server capability disabled
- Uses default Advanced Parameters
- Permits changes to Advanced Parameters
Operational
- Full support for client and server
capability
- Uses user defined Advanced
Parameters
œ
1
1
2
3
4
5