10  TROUBLESHOOTING 
10.1  TROUBLESHOOTING UPS CONNECTION 
The SNMP/Web adapter front panel features a LED marked ‘UPS’. This LED should be OFF in normal 
conditions. If the LED is ON then there is a problem in the communication with the UPS. 
NOTEIt may take up to one minute for the adapter to synchronise the communication with the UPS
Also, the SNMP/Web adapter will signal a Communication Lost alarm if communication with the UPS is 
lost and cannot be re-established. 
 
10.1.1  3-ph SNMP/Web plug-in adapter 
The 3-ph plug-in adapter features a dip-switch to configure the card logical address. This setting is 
critical when two or more cards are installed in the same UPS system. The address of each card MUST 
be unique – refer to the Installation section of the Installation Guide for details.  
NOTE: In case of address collision with other SNMP/Web adapters the UPS alarm web page will show 
the following notice: “Address collision. Check adapter configuration” 
 
10.1.2  1-ph SNMP/Web external adapter 
The 1-ph external adapter connects to the UPS through cables. In case of problems in the 
communication with the UPS check the cabling.  
The cable for connecting the adapter to the UPS is normally provided with the UPS. Note that two types 
of communication are possible: 
•  Intelligent (serial) communication: use VIC-23 or IMV-I cable or straight 1:1 serial cable 
•  Contact interface communication: use VIC-25 or IMV-C serial cable 
The actual cable to be used will depend on the actual UPS make and model – refer to applicable UPS 
documentation and accessories. In any case, make sure the proper cable is used. 
 
 
10.2  TROUBLESHOOTING LOCAL CONNECTION 
For troubleshooting problems in local (serial) console connection to the adapter refer to the following 
table. 
 
Problem Recommended 
resolution 
Port already in use – e.g. Windows HyperTerminal 
reports the following problem: 
Close all applications and services that are 
currently using the port selected for the 
connection to the device.  
 
Attempt a new connection. 
Check the serial cable (a straight 1:1 serial cable 
is required) and its connection. 
Check the settings of the terminal application: 
 
115,200bps, 8 data bits, 1 stop bit,  
 parity 
none, 
flow control none 
Cannot connect to the adapter 
Verify username and password used.  
Verify that the user has been correctly defined 
and configured by the administrator. 
Cannot login to the local console 
Cannot use interactive menus 
Check the settings of the terminal application: 
 
Terminal emulation VT-100 
Modifications reserved 
Page 53/58 
OPM_CNT_SNM_BAS_CRD_1GB_V012.doc 
Operating Manual SNMP/Web Adapter