Liebert DS 用户手册
Piping Schematics
94
Figure 69 Primary connection locations—downflow, air-Cooled, 53-77kW (15-22 ton), semi-hermetic
compressor models
Point
Description
X
inches (mm)
Y
inches (mm)
Connection Size / Opening
inches (mm)
R
Refrigerant Access
82-3/4 (2102)
13-7/8 (352)
16-7/16 x 4 (418 x 102)
53kW (15ton) / 70 & 77kW (20 & 22ton)
L1
Liquid Line System 1
97 (2464)
16-7/8 (428)
1/2 / 5/8 Cu Sweat
L2
Liquid Line System 2
93-5/16 (2370)
16-7/8 (428)
1/2 / 5/8 Cu Sweat
G1
Hot Gas Discharge 1
90-5/8 (2302)
16-5/8 (422)
7/8 / 1-1/8 Cu Sweat
G2
Hot Gas Discharge 2
88 (2235)
16-5/8 (422)
7/8 / 1-1/8 Cu Sweat
CD
Condensate Drain *
69-1/4 (1759)
30 (762)
3/4 FPT
W/ Optional Pump
69-1/4 (1759)
30 (762)
1/2 Cu Sweat
HUM
Humidifier Supply Line
76-1/2 (1943)
29 (736)
1/4 Cu Sweat
ECS**
Econ-O-Coil Supply
78-5/8 (1997)
22-1/4 (565)
2-1/8 Cu Sweat
ECR**
Econ-O-Coil Return
72 (1829)
29 (737)
2-1/8 Cu Sweat
HS
Hot Water Reheat Supply
Consult Factory
HR
Hot Water Reheat Return
Consult Factory
E1
Electrical Connection (High Volt)
78-1/2 (1994)
31-1/8 (790)
2-1/2
E2
Electrical Connection (High Volt)
75-3/8 (1915)
31-1/8 (790)
2-1/2
LV1
Electrical Connection (Low Volt)
1-7/8 (48)
28-1/2 (724)
7/8
LV2
Electrical Connection (Low Volt)
1-7/8 (48)
30-1/4 (768)
7/8
LV3
Electrical Connection (Low Volt)
1-7/8 (48)
32 (813)
7/8
B1
Blower Outlet (15 x 15)
23-1/8 (587)
18-1/16 (459)
18-3/4 x 16-1/16 (476 x 408)
Blower Outlet (15 x 11)
27-3/4 (705)
18-1/16 (459)
14-3/4 x 16-1/16 (375 x 408)
B2
Blower Outlet (15 x 15)
50-3/8 (1280)
18-1/16 (459)
18-3/4 x 16-1/16 (476 x 408)
Blower Outlet (15 x 11)
54-3/8 (1381)
18-1/16 (459)
14-3/4 x 16-1/16 (375 x 408)
* Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
with all local codes.
** Supplied on Dual-Cool systems only (4-pipe system)
Section A-A
Front View
16-1/16"
(408 mm)
A
A
X
Y
O
35"
(889mm)
All dimensions
from rear corner
of unit including
panels
from rear corner
of unit including
panels
Tolerance on all
piping dimensions
is ± 1/2" (13mm)
piping dimensions
is ± 1/2" (13mm)
109"
(2769mm)
Front of Unit
Note: Drawing not to scale
DPN000928
Rev. 2
Rev. 2
4" (102mm)
LV3
LV2
LV1
ECS
HUM
CD
ECR
E1 E2
B2
16-7/16"
(418mm)
L1
L2
G1 G2
Blower
Outlet
B1
Blower
Outlet
R