Piping Schematics
94
Figure 69 Primary connection locations—downflow, air-Cooled, 53-77kW (15-22 ton), semi-hermetic 
compressor models
Point
Description
X
inches (mm)
Y
inches (mm)
Connection Size / Opening
inches (mm)
R
Refrigerant Access
82-3/4 (2102)
13-7/8 (352)
16-7/16 x 4 (418 x 102)
53kW (15ton) / 70 & 77kW (20 & 22ton)
L1
Liquid Line System 1
97 (2464)
16-7/8 (428)
1/2 / 5/8 Cu Sweat
L2
Liquid Line System 2
93-5/16 (2370)
16-7/8 (428)
1/2 / 5/8 Cu Sweat
G1
Hot Gas Discharge 1
90-5/8 (2302)
16-5/8 (422)
7/8 / 1-1/8 Cu Sweat
G2
Hot Gas Discharge 2
88 (2235)
16-5/8 (422)
7/8 / 1-1/8 Cu Sweat
CD
Condensate Drain *
69-1/4 (1759)
30 (762)
3/4 FPT
 W/ Optional Pump
69-1/4 (1759)
30 (762)
1/2 Cu Sweat
HUM
Humidifier Supply Line
76-1/2 (1943)
29 (736)
1/4 Cu Sweat
ECS**
Econ-O-Coil Supply
78-5/8 (1997)
22-1/4 (565)
2-1/8 Cu Sweat
ECR**
Econ-O-Coil Return
72 (1829)
29 (737)
2-1/8 Cu Sweat
HS
Hot Water Reheat Supply
Consult Factory
HR
Hot Water Reheat Return
Consult Factory
E1
Electrical Connection (High Volt)
78-1/2 (1994)
31-1/8 (790)
2-1/2
E2
Electrical Connection (High Volt)
75-3/8 (1915)
31-1/8 (790)
2-1/2
LV1
Electrical Connection (Low Volt)
1-7/8 (48)
28-1/2 (724)
7/8
LV2
Electrical Connection (Low Volt)
1-7/8 (48)
30-1/4 (768)
7/8
LV3
Electrical Connection (Low Volt)
1-7/8 (48)
32 (813)
7/8
B1
Blower Outlet (15 x 15)
23-1/8 (587)
18-1/16 (459)
18-3/4 x 16-1/16 (476 x 408)
Blower Outlet (15 x 11)
27-3/4 (705)
18-1/16 (459)
14-3/4 x 16-1/16 (375 x 408)
B2
Blower Outlet (15 x 15)
50-3/8 (1280)
18-1/16 (459)
18-3/4 x 16-1/16 (476 x 408)
Blower Outlet (15 x 11)
54-3/8 (1381)
18-1/16 (459)
14-3/4 x 16-1/16 (375 x 408)
* Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain a factory-installed condensate trap. Do 
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply 
with all local codes.
** Supplied on Dual-Cool systems only (4-pipe system)
Section A-A
Front View
16-1/16"
(408 mm)
A
A
X
Y
O
35"
(889mm)
All dimensions 
from rear corner 
of unit including 
panels
Tolerance on all 
piping dimensions 
is ± 1/2" (13mm)
109"
(2769mm)
Front of Unit
Note:  Drawing not to scale
DPN000928
Rev. 2
4" (102mm)
LV3
LV2
LV1
ECS
HUM
CD
ECR
E1 E2
B2
16-7/16"
(418mm)
L1
L2
G1 G2
Blower 
Outlet
B1
Blower 
Outlet
R