Chapter 8: Managing External Devices 
 
 
179
 
 
States of Managed Sensors 
An environmental sensor shows the state after being managed. 
Available sensor states vary depending on the sensor type -- numeric or 
discrete sensors. For example, a contact closure sensor is a discrete 
(on/off) sensor so it switches between three states only -- unavailable, 
alarmed and normal. 
Note: Numeric sensors use numeric values to indicate the environmental 
or internal conditions while discrete (on/off) sensors use alphabetical 
characters only to indicate the state changes. 
Sensor state 
Applicable to 
unavailable 
All sensors 
alarmed 
Discrete sensors 
normal 
All sensors 
below lower critical 
Numeric sensors 
below lower warning 
Numeric sensors 
above upper warning 
Numeric sensors 
above upper critical 
Numeric sensors 
 
 
"unavailable" State 
The unavailable state means the connectivity to the sensor is lost. 
The EMX pings all managed sensors at regular intervals in seconds. If it 
does not detect a particular sensor for three consecutive scans, the 
unavailable state is displayed for that sensor. 
When the communication with a contact closure sensor's processor is 
lost, all detectors (that is, all switches) connected to the same sensor 
module show the "unavailable" state. 
Note: When the sensor is deemed unavailable, the existing sensor 
configuration remains unchanged. For example, the ID number assigned 
to the sensor remains associated with it. 
The EMX continues to ping unavailable sensors, and moves out of the 
unavailable state after detecting the sensor for two consecutive scans.