Appendix A: Using Raritan Asset Management Sensors with the EMX 
 
 
333
 
 
Connecting AMS-M2-Z Asset Sensors (Optional) 
The AMS-M2-Z is a special type of asset sensor that functions the same 
as regular MASTER asset sensors with the following differences: 
 
It provides two RJ-45 connectors 
 
Multiple AMS-M2-Z asset sensors can be daisy chained 
 
Only two tag ports are available on each AMS-M2-Z so only two 
asset tags can be connected 
This product is especially useful for tracking large devices such as SAN 
boxes in the cabinet. 
 
Item 
Description 
RJ-45 connectors 
Tag ports 
 
To connect the AMS-M2-Z asset sensors to the EMX: 
1.  Connect the AMS-M2-Z to the EMX via a Category 5e/6 cable. 
a.  Connect one end of the cable to the RJ-45 port labeled "Input" 
on the AMS-M2-Z. 
b.  Connect the other end of the cable to the FEATURE port on the 
EMX. 
2.  Affix an asset tag to the IT device and connect this asset tag to the 
AMS-M2-Z by plugging the tag connector into the tag port on the 
AMS-M2-Z. See 
Connecting Asset Sensors to the EMX
 (on page 
24) for details. 
3.  If necessary, daisy chain multiple AMS-M2-Z to track more than two 
IT devices via this EMX.  
a.  Verify that the Category 5e/6 cable length is within the limitation. 
See 
AMS-M2-Z Daisy-Chain Limitations
 (on page 334) for the 
cable length limitations. 
b.  Connect one end of the Category 5e/6 cable to the RJ-45 
connector labeled "Output" on the AMS-M2-Z being connected to 
the EMX.