Operating Characteristics - Controller Modes 
Revision 5 
  HC900 Hybrid Controller Installation and User Guide 
113 
9/03  
Table 21 - Controller Behavior in Mode Transition  
Initial Mode 
New Mode 
Controller Behavior 
PROGRAM RUN 
Validate configuration database. 
Reset all I/O scanners. 
Upon startup, initiate Cold Start sequence. 
Diagnostic: Identify and configure all I/O racks and modules. (All 
output modules are configured with Failsafe values.  Any modules 
not included in the configuration are configured with default values, 
which causes outputs to be Off.) 
While in transition, all output modules are Off; when transition 
procedures are completed, Function Block processing begins, and 
output values are set to Function Block output values. 
Any calibration process that was in progress is immediately aborted, 
and the results are discarded. 
PROGRAM OFFLINE 
Same as PROGRAM to RUN transition, except that Function Blocks 
are not processed, and outputs remain Off. 
Any calibration process that was in progress is immediately aborted, 
and the results are discarded. 
RUN  
PROGRAM 
Set all channels of all output modules to Off. 
Set all output module Failsafe values to the Off state. 
Turn off the LED indications on all output modules. 
OFFLINE 
 
PROGRAM 
Same as RUN to PROGRAM transition. 
Any calibration process that was in progress is immediately aborted, 
and the results are discarded. 
RUN 
 
OFFLINE 
Freeze output module channels.  
Freeze Force LED indications on all output modules. 
OFFLINE RUN 
Function Block execution starts immediately. 
Any calibration process that was in progress is immediately aborted, 
and the results are discarded.