Diagnostics and Troubleshooting - User Interface 
124 
  HC900 Hybrid Controller Installation and User Guide 
Revision 5 
  
9/03 
Table 27 - Controller Module Diagnostics 
OI Screen 
Item  
OI Screen 
Item Value 
Number of 
LED 
Strobes  
Possible Cause 
Control File Action 
User Action 
COMPORT GOOD 
N/A 
N/A 
N/A 
N/A 
 
FAILED 
N/A 
One of the Comm 
ports is reporting a 
physical or data link 
failure 
 
Refer to related Comm 
port diagnostic below. 
1. Check connections 
2. Access the Comm 
port diagnostics 
screen 
3. Replace CPU 
IO GOOD 
N/A 
N/A 
N/A 
N/A 
 MODULE 
ERROR 
One of the module 
diagnostics in the 
associated rack is set 
to WRONG MODULE, 
NO COM/MISSING 
MODULE (if the 
communications is 
failing due to the 
module not installed), 
BAD MODULE, or 
BAD CHANNEL. 
Refer to related Module 
diagnostic below. 
1. Access the I/O 
Module diagnostics 
screen. 
2. Install proper module 
3. Replace faulty 
module 
 
HI TEMP 
One of the module 
diagnostics in the 
associated rack is set 
to HI CJ 
TEMPERATURE. 
Refer to HI CJ 
TEMPERATURE in 
Module diagnostics 
See module 
diagnostic actions for 
HI CJ TEMP 
 RACK 
BACKPLANE 
FAIL 
6 The 
Main 
CPU/Scanner is 
unable to successfully 
communicate to any 
modules that are in its 
SPI backplane. 
All associated module 
diagnostics are set to 
MODULE NO COMM. 
Refer to MODULE NO 
COMM diagnostic for 
further details. 
 
1. Remove modules 
and check for bent 
pins on connectors. 
2. Reinsert modules 
one at a time and 
note which module 
the diagnostic 
reoccurs, and 
replace that module. 
3. Cycle power to the 
rack. 
4. Replace the power 
supply. 
5. Replace the rack. 
6. Replace the CPU 
board.