Appendix B Installation of Remote Termination Panels (RTPs) - Analog Input
184
HC900 Hybrid Controller Installation and User Guide
Revision 5
9/03
Analog Input
8 Point Analog Input
Step Action
1
ATTENTION: RTP is not for use with thermocouples.
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
Mount RTP cable assembly to HC900 Controller (Figure 60).
•
Remove appropriate key tabs from terminal block to allow mating with the module. See page 64.
•
Connect desired cable to AI module at controller. Choose from:
900RTC-L010 Remote Terminal Low Voltage Cable Assembly, 1.0 meters long
900RTC-L025 Remote Terminal Low Voltage Cable Assembly, 2.5 meters long.
900RTC-L050 Remote Terminal Low Voltage Cable Assembly, 5.0 meters long
900RTC-L010 Remote Terminal Low Voltage Cable Assembly, 1.0 meters long
900RTC-L025 Remote Terminal Low Voltage Cable Assembly, 2.5 meters long.
900RTC-L050 Remote Terminal Low Voltage Cable Assembly, 5.0 meters long
•
Install AI module label onto the module connector cover.
•
Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 60).
shields must be grounded as described in the shield grounding section (page 60).
2
Mount RTP to DIN rail.
•
Latch to rail. See page 205.
•
Connect cable to RTP.