National Instruments cFP-DO-403 用户手册
[c]FP-DO-403
10
ni.com
Caution
For Zone 2 applications, install a protection
device across the external power supply and the COM
terminal. The device must prevent the external power
supply voltage from exceeding 42 V if there is a transient
overvoltage condition.
terminal. The device must prevent the external power
supply voltage from exceeding 42 V if there is a transient
overvoltage condition.
Special Conditions for Hazardous Locations Use in Europe
The [c]FP-DO-403 has been evaluated as EEx nC IIC T4
equipment under DEMKO Certificate No. 03 ATEX 0251502X.
Each module is marked
equipment under DEMKO Certificate No. 03 ATEX 0251502X.
Each module is marked
II 3G and is suitable for use in Zone 2
hazardous locations.
Specifications
These specifications are typical for –40 to 70 °C unless otherwise
noted. Specifications are subject to change without notice.
noted. Specifications are subject to change without notice.
Output Characteristics
Number of channels.......................... 16
Output type ....................................... Sinking
Voltage range .................................... 5 to 30 VDC
Output impedance............................. 0.12
Ω
(0.12 V drop at 1 A)
Maximum current
Per channel ................................. 2 A
All channels
All channels
FP-DO-403........................... 16 A
2
cFP-DO-403......................... 16 A
2
at –40 to 60 °C
12 A
2
at 60 to 70 °C
Maximum OFF state leakage............ 50
μA
Output delay time ............................. 50
μs
Physical Characteristics
Indicators .......................................... Green POWER and
READY indicators, 16 green
output state indicators
output state indicators
Weight
FP-DO-403 ................................. 140 g (4.8 oz)
cFP-DO-403 ............................... 110 g (3.7 oz)
cFP-DO-403 ............................... 110 g (3.7 oz)