National Instruments BridgeVIEW 用户手册

下载
页码 455
Chapter 3
Tag Configuration
© National Instruments Corporation
3-45
Note
Although you can configure these parameters, it is highly recommended you 
maintain the default values.
Table 3-12.  Configurable Memory Allocation Parameters
Parameter
Description
Default Value
System Events 
display (lines
Determines the maximum number of lines of text to be 
displayed in the System Errors and Events display of the 
Engine Manager.
20 
Error Message 
repeat rate 
(seconds)
Determines the time, in seconds, that recurring error 
messages should be repeated to the user. For example, 
an undefined tag message error repeats only after this 
value is exceeded.
600 secs 
(10 minutes)
Event History 
Buffer size 
(elements) 
Determines the length, in elements of the queue that 
handles event information sent from the Engine to 
.evt
files.
2000
Historical Log 
Queue (elements)
Determines the length, in elements, of the queue that 
handles data sent from the engine to the Citadel 
historical database.
2000
Server Input Queue 
size (elements) 
Determines the length, in elements, of the queue that 
handles data sent from the device servers to the Engine.
2000
Server Input Queue 
binary size (bytes) 
Determines the length, in bytes, of the queue that 
handles binary data (string tags) sent from the device 
servers to the Engine.
2000
Server Output 
Queue size 
(elements) 
Determines the length, in elements, of the queue that 
handles data sent from the Engine to the device servers.
2000
Server Output 
Queue binary size 
(bytes) 
Determines the length, in bytes, of the queue that 
handles binary data (string tags) sent from the Engine to 
the device servers.
2000
Server Shutdown 
timeout (seconds) 
Determines the time, in seconds, the Engine waits for all 
active device servers to shutdown before asking the user 
if the servers are to be forcefully terminated.
30