Chapter 8
Servers
© National Instruments Corporation
8-5
Browser utility. You can remove these servers from the server list by 
selecting the Unregister Server option in the Server Browser utility. 
How Do You Use OPC Servers with BridgeVIEW?
BridgeVIEW can communicate with any server implementing the OPC 
Foundation OPC Server interface, a Microsoft COM-based standard. 
BridgeVIEW automatically finds all OPC Servers installed in your system 
and searches the network for OPC servers on other machines. Unlike 
Device Servers, OPC Servers do not store information in the Common 
Configuration Database, rather BridgeVIEW reads any available 
information about server capabilities and items from the server directly.
OPC Servers are listed in the Server Name List when you configure 
a BridgeVIEW tag using the Tag Configuration Editor. To connect a 
BridgeVIEW tag to an OPC Server item, you select the server and enter 
or choose the item name along with other parameters you might need to 
specify, such as the access path. You also create I/O Groups for the items, 
specifying update rate and deadband information for each group. Each 
BridgeVIEW I/O Group created in the Tag Configuration Editor is 
automatically mapped to an OPC Group in the OPC Server with the 
same attributes.
OPC Servers have an optional interface called the Server Browse Address 
Space Interface. If a server supports this interface, BridgeVIEW can query 
it to find which items are available from the server and display them in the 
item list when the server is selected in the Tag Configuration dialog box. 
In this case, the Browse button in the Tag Configuration dialog box is 
enabled, and you can press this button to view the hierarchical 
organization of the server Item IDs.
You can also view the OPC Server Items and their attributes using 
the Server Browser utility. Launch the Server Browser by selecting 
Projects»Server Tools»Server Browser… or pressing the Server 
Browser…
 button on the Engine Manager display.