Chapter 1 Introduction
© National Instruments Corporation 1-9 BridgeVIEW User Manual
with the BridgeVIEW Engine to read and write tag values, acknowledge 
alarms, access historical data, and read and write tag attributes.
BridgeVIEW makes development of operator graphic displays easy and 
fast. Floating palettes provide controls and functions necessary to develop 
effective HMI and SCADA applications. The Controls palette provides a 
number of predefined objects, selected from the automation symbol library, 
for building your HMI. The Functions palette provides a set of functions 
and VIs you can use for I/O, analysis, historical data, and networking.
BridgeVIEW Engine
Th
 is the heart of the BridgeVIEW System. It runs as 
a separate process, independent of your HMI application. This minimizes 
interference between the Engine and your HMI. The BridgeVIEW Engine 
maintains the Real-Time Database of all tag values and alarm states. It 
reads values from the various device servers. These values are scaled and 
compared with their alarm limits. If a tag is in an alarm state, the Engine 
generates appropriate events and logs them to disk.
The Real-Time Database (RTDB) is an in-memory snapshot of the state of 
all tags in the system. If a tag value changes more than its update deadband, 
or its alarm state changes, the RTDB is updated. Along with tag values, the 
RTDB also stores status, date, time, and alarm information. 
Device Servers
 is the application that communicates with the I/O devices 
such as PLCs and plug-in cards. Several National Instruments device 
servers are written to a National Instruments standard client/server 
Application Programming Interface (API) for the BridgeVIEW 
Engine. BridgeVIEW also communicates with OPC and DDE Servers. 
There are different servers for different device manufacturers and 
communication networks.
The device servers that support the BridgeVIEW Engine are stand-alone 
programs launched by the BridgeVIEW Engine, and thereafter run in the 
background, reading selected input items and writing them on demand. 
Each server either is configured by BridgeVIEW when tags are created, 
or has a specific configuration utility that determines communication 
parameters, I/O poll rates, and device addresses. A server completes 
operation only when the BridgeVIEW Engine shuts down.
Input items are polled by servers at a rate determined by the BridgeVIEW 
I/O group configuration. For each input item, the device server passes