National Instruments BridgeVIEW 用户手册

下载
页码 455
Appendix A
HMI Function Reference
A-56
© National Instruments Corporation
Read Tag (bit array)
Use the Read Tag (bit array) VI to read the latest value for a given bit array tag from the 
Real-Time Database. For immediate polling of the tag value, leave timeout (secs) unwired. 
To wait until the value is updated before reading it, wire a timeout value, in seconds, to the 
timeout input. The Read Tag (bit array) VI returns with the most recent Real-Time Database 
value when it is updated, the timeout is exceeded, or the Real-Time Database is shutting 
down, whichever occurs first. Use the changed? output to determine whether the value 
changed since the last read.
Note
Use a separate Read Tag (bit array) VI for each tag you want to monitor. Do not 
put the Read Tag (bit array) VI in a loop to read a different tag each iteration of 
the loop. This results in slower program performance. The Read Tag (bit array) VI 
is designed to save information about the tag internally for efficient operation. 
This information is updated every time the tag name changes.
tag name is the name of the bit array tag.
timeout (secs) (0) specifies how many seconds to wait for the tag value to 
be updated in the Real-Time Database before reading the Real-Time 
Database for the latest value. If timeout is the default value of 0, the Read 
Tag (bit array) VI reads the Real-Time Database immediately and returns 
the tag value without waiting. If timeout is –1, Read Tag (bit array) waits 
indefinitely until the tag value is updated, or the BridgeVIEW Engine shuts 
down, whichever occurs first. If a timeout occurs before the value is 
updated, Read Tag (bit array) returns the most recent value from the 
Real-Time Database, and timeout is set to TRUE. 
in alarm is TRUE if the tag is in alarm.
value status returns the status of the value. If value status is greater than 
or equal to 0, the value returned by Read Tag is valid and there is a warning 
about the tag value. If value status is less than 0, either the device server 
has reported an error indicating there is a problem with the tag, or 
BridgeVIEW has reported an error indicating there is a problem using 
the tag.