National Instruments BridgeVIEW 用户手册

下载
页码 455
Appendix A
HMI Function Reference
© National Instruments Corporation
A-65
Write Tag (discrete)
Use the Write Tag (discrete) VI to update the Real-Time Database with a new value for 
memory, output, and Input/Output tags. The value also is sent to the server if it is an output 
or Input/Output tag. If the tag is an input only tag, the Write Tag (discrete) VI causes a system 
error because input tags only can be updated by servers. If the tag is configured as an 
Input/Output tag, the tag value is passed to the server when Write Tag (discrete) VI is called 
but not written to the RTDB. The RTDB is updated with the new value when the server polls 
it and passes it back to the BridgeVIEW Engine. This maintains correct time synchronization 
in the RTDB.
tag name is the name of the output tag.
value is the value written to the output tag.
generate event (F) determines whether a user change event is generated 
for the write operation on the tag. If the tag is configured with event logging 
on, this tag event can be displayed in the Event History Display in your 
HMI and logged to a .
evt
 file. By default, generate event is FALSE. 
status returns the current status of the value written in the Real-Time 
Database. If status is greater than or equal to 0, the Write Tag (discrete) 
operation was successful. If status is less than 0, either the device server 
has reported an error indicating there is a problem with the tag, or 
BridgeVIEW has reported an error indicating there is a problem using 
the tag.
error indicates that an error occurred when executing the Write Tag 
(discrete) VI, or that the status of the tag is bad. See status for the specific 
error condition.
shutdown indicates that the BridgeVIEW Engine is shutting down. You 
can use shutdown to exit any loop that uses the Write Tag (discrete) VI.