1592010860 XWEB5000 stp GB r1.1 2012.06.22.doc                                     XWEB5000 
6/48 
 
2. INSTALLATION 
Do  not  open  XWEB.  Its  opening  makes  its  warranty  invalid.  However,  to  install 
XWEB you need: 
  One blade and one cross screwdrivers 
  Mouse PS2 
  Keyboard PS2 
  Standard VGA screen (no high definition/HDMI) 
 
To  install  XWEB,  please  refer  to  the  picture  below  which  represents  the  back  of 
XWEB. Apply then following procedure: 
 
1.  XWEB  has  grounding receptacle.  Verify the  implant in  which  it  will  be  connected to 
adopt electrical ground protection;  
2.  Fix XWEB at its operating position.  In 
case  of  placement  on  a  table  insert 
provided  rubber feet.  In  case  of  usage 
on  rack,  use  provided  brackets  and 
screws. 
3.  To  connect  XWEB  to  the  electrical 
network  use  provided  power  supply 
cable(1).  Power  supply  cable  shall 
always  be  easily  accessible  by  an 
operator.  Do  not  power  the  system 
on.
  
4.  Connect  RS485  network,  relays  and 
digital input (3). 
5.  Connect  to  telephonic  line  network 
and/or to LAN (4). 
6.  Connect  keyboard  and  mouse  with 
provided cable (5). 
7.  Connect monitor (5). 
8.  Connect  printer  to  USB  or  parallel 
receptacles. 
9.  Connect  optional  external  modem  (7). 
Its cable  shall be  maximum  10 meters 
long. 
10.  Power  the  system  on,  pressing  and 
releasing button (2). 
 
 
  Connect  XWEB  to  the  electrical  network  with 
provided  cord  before  any  servicing  operation. 
This is for personnel and system safeguard. 
 
  Operators  shall  avoid  direct  passage  of 
electronic  devices  that  can  cause  electric 
discharges and damage the device itself; 
  Power  supply  voltage  shall  not  differ  from  the 
one  required.  It  can  seriously  damage  the 
system; 
  Mistaken  connections  can  be  dangerous  and 
compromises  operators’  safety.  Moreover  they 
can damage the system and/or other connected 
instruments. 
  Adopt  one  or  more  external  isolator  switches to 
separate devices to power supply network. They 
shall easily accessible. 
  Do  not  use  XWEB  in  environments  with 
inflammable gas. 
  Do not modify XWEB in any way.