IMC Networks 6 用户手册

下载
页码 28
 
5
 
Wiring Instruction Guidelines for iMediaChassis/20-2DC 
1.  Connection of a suitable grounding conductor to the grounding terminal 
at each power supply module (a minimum 14AWG copper conductor 
should be suitable based on a 15A circuit breaker requirement).  
2.  Connection of suitable supply wiring to the plus and minus terminals at 
each power supply module (a minimum 14AWG copper conductors is 
considered suitable based on the 11A input maximum).  The input 
terminal block at the power supply module is suitable for 22-14 AWG 
copper wire.  
3.  A suitable listed circuit breaker shall be provided in the building 
installation as the unit's disconnect device.  The branch circuit rating (i.e. 
minimum 15A listed circuit breaker, etc.). 
 
DC Power Supply Module Wiring Instructions 
The following diagram shows the wiring configuration for a -48 VDC power supply 
module for the iMediaChassis/20-2DC. 
 
 
 
 
 
NOTE 
The chassis is protected against incorrect wiring configurations.  When wired 
incorrectly, the chassis will not function, but no damage will occur.