RuggedCom RX1510 用户手册

下载
页码 45
5. EMI And Environmental Type Tests
RuggedCom® RuggedBackbone™
43
RX1510 Installation Guide Rev 104
Test
Description
Test Levels
Enclosure Contact
+/-2kV, +/-4kV, +/- 8kV
IEEE C37.90.3
ESD
Enclosure Air
+/-4kV, +/-8kV, +/-15kV
IEEE C37.90.2
Radiated RFI
Enclosure ports
35 V/m
Signal ports
+/- 4kV @ 2.5kHz
D.C. Power ports
+/- 4kV
A.C. Power ports
+/- 4kV
IEEE C37.90.1
Fast Transient
Earth ground ports
+/- 4kV
Signal ports
2.5kV common mode @1MHz
D.C. Power ports
2.5kV common, 1kV diff. mode@1MHz
IEEE C37.90.1
Oscillatory
A.C. Power ports
2.5kV common, 1kV diff. mode@1MHz
Signal ports
5kV (Fail-Safe Relay output)
D.C. Power ports
5kV
IEEE C37.90
H.V. Impulse
A.C. Power ports
5kV
Signal ports
2kVAC
D.C. Power ports
1.5kVDC
IEEE C37.90
Dielectric Strength
A.C. Power ports
2kVAC
a
 Meets Class 2 requirements for an all-fiber configuration. Meets Class 1 requirements for copper ports.
Table 5.2. IEEE 1613 (C37.90.x) EMI Immunity Type Tests
a
Test
Description
Test Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40°C, 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
+85°C, 16 Hours
IEC 60068-2-30
Humidity (Damp Heat, Cyclic)
Test Db
95% (non-condensing), 55°C , 6 cycles
IEC 60255-21-1
Vibration
2g @ (10 - 150) Hz
IEC 60255-21-2
Shock
30g @ 11mS
Table 5.3. Environmental Type Tests