GE EX2100 用户手册

下载
页码 118
EX2100 User’s Guide  GEH-6632
Chapter 5  Diagnostic Interface-Keypad 
••••
 5-5
Reading the Display
The keypad displays information as both text and animated graphics. There are two
types of content screens, selected by pressing the corresponding Navigation button:
Status and Menu.
The Status Screen (Figure 5-2) is the default screen that displays after exciter
startup, following an initialization screen. It uses animated meters with associated
text to present exciter performance data. An alternate Status Screen can also be
accessed (see Status Screen).
FVR Feedback
0.0 Volts
FldCurrAmps
0.00 Amps
-30%
0%
150%
100%
Vmag
Freq_Hz
Imag
Watts
Balance Meter
Vars
0.00
0.00
0.00
60.00
0.00
0.00
-30%
0%
150%
100%
Animated
Meters
Text Identifying
Exciter Variable
Heartbeat
Fault State
Limiter
Auto Mode
Running
Online
Figure 5-2.  Status Screen Example
The Menu Screen (see Figure 5-3) lists and provides access to menu-based
functions for adjusting parameters, running wizards, and viewing faults (see Menu
Selections
).
Main Menu
Fault List
Alarms
Application data
Diagnostic and utility functions
General setup
I/O interface
Alarm String
Figure 5-3.  Menu Screen Example
The Exciter Health and State Icons continually show on the right hand side of all
display screens. They indicate if the exciter is functioning correctly and show its
running state. These icons are displayed in five functional groups, as shown below.
You can change the display units and adjust the display contrast, if needed.