GFK-1004B
Chapter 5  The Station Manager
Table 5-9.  Log Event Definitions
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Log Event
(Hexadecimal)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Cause
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Powerup.  A log entry of this event will appear every time
the Ethernet Interface is restarted or powered up.
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
2
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
System events.
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
8
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
PLC Driver events.
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
b
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Service Agent events.
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
c
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
LLC events.
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
11
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
IP Layer events
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
12
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
TCP Layer events
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
16
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ARP Layer events
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
18
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Network Layer events
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
1b
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
SRTP Server events
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
1c
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Channel API
Refer to Chapter 6, Troubleshooting, for information on interpreting the logged events.
LOGIN Command
The LOGIN command has the form:
LOGIN
The LOGIN command will be followed by a prompt of the form:
Password:
You should enter your password (which will not be echoed).  If the password matches
the current password for the Modify level, you will receive a confirmation message and
you will be allowed access to the Modify commands.  If the password does not match,
then an error message is displayed and the security level is not changed.
Please note that all characters which are typed after the password prompt except for the
Enter key are assumed to be part of the password.  Specifically, the delete and backspace
characters do not have their usual meaning and are interpreted simply as password
characters.  Passwords are limited to 8 characters and all characters after the eighth are
ignored.  Unlike other inputs, the password does not need to be enclosed with double
quotes to achieve case sensitivity.
The factory default password is:  system (lower case).