GE GFK-2251 用户手册

下载
页码 62
 
GFK-2251 
Chapter 4  Connectors and Cabling 
4-7 
 
4
 
  
 
Serial Communication Ports 
The COM1and COM2 serial ports are available on the side panel. The COM3 serial port is 
used by the touchscreen and is not accessible to the user. The standard 9-pin D-sub 
connector pin out is shown below.   
 
RS-232C Name 
Pin 
Assignment 
CF 
DCD (Data Carrier Detect) 
BB 
RX (Receive Data) 
BA 
TX (Transmit Data) 
CD 
DTR (Data Terminal Ready) 
AB 
GND (Signal Ground) 
CC 
DSR (Data Set Ready) 
CA 
RTS (Request to Send) 
CB 
CTS (Clear to Send) 
CE 
RI (Ring Indicator) 
Shielding 
The D type connector covers should be metallized plastic or die cast metal and terminated 
with 360-degree termination of the shield, as illustrated in Figure 4-3 below. 
 
Figure 4-3. High Frequency Grounding 
Grounding 
Serial cables (COM1 and COM2) must be shielded and grounded in order to maintain CE 
Mark compliance, provide higher EMC immunity, and satisfy the requirements of 
IEC/EN61000-4-4 and IEC/EN61000-4-5. The shield conductor should remain continuous 
to the unit, and insulation should be removed only at the grounding point. The grounding 
should be such that a 360-degree contact is made to the cable shield. Figure 4-4 shows 
an example with the insulating cover of the cable stripped back.