Emerson GXT2-PP20KRT208 用户手册

下载
页码 36
Specifications
29
10.0 S
PECIFICATIONS
Table 5
Parallel POD specifications
Model Number
Liebert GXT2-PP20KRT208
Model Rating
20,000VA / 16,000W at 120/208 or 120/240 VAC
Dimensions, in (mm)
Unit, W x D x H in. (mm)
16.94 x 9.85 x 16.61 (430 x 250 x 422)
Shipping, W x D x H in. (mm)
23.05 x 16.74 x 19.38 (585 x 425 x 492)
Weight, lb (kg)
Unit
41.89 (19)
Shipping
48.94 (22.2)
Input AC Parameters
Nominal Operating Frequency
50 or 60 Hz
Nominal Operating Voltage
120/208 or 120/240 VAC
Input Power Connection
Hardwire Terminal Block 3W + G (L-L-N-G)
Output AC Parameters
Voltage
120/208 or 120/240 VAC
Output Connections
Hardwire Terminal Block 3W + G (L-L-N-G);
Frequency
50 Hz or 60 Hz, Nominal
Agency
Safety
UL / c-UL Listed as accessory for UPS
ESD
EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility
EN61000-4-3, Level 3, Criteria A
Conducted Immunity
EN61000-4-6 Level 3, Criteria A
EFT / Burst
EN61000-4-4, Level 4, Criteria A
Surge
EN61000-4-5, Level 3, Criteria A
ANSI C62.41 (IEEE 587) Category A (Level 3) & B (Level 1)
Transportation
ISTA 1A
Table 6
Paralleling cable kit dimensions and weight
Model Number
Liebert GXT2-20KPC-6 (1 required for each UPS)
Dimensions, in (mm)
Shipping, W x D x H in. (mm)
15.76 x 15.76 x 4.02 (400 x 400 x 120)
Weight, lb (kg)
Shipping
13.89 (6.3)