Emerson 1000 用户手册

下载
页码 32
Specifications
22
8.0
S
PECIFICATIONS
Table 6
Liebert PSI XR specifications
Model Number
PS1000RT3-120XR
PS1000RT3120XRW
PS1500RT3-120XR
PS1500RT3120XRW
PS2200RT3-120XR
PS2200RT3120XRW
PS3000RT3-120XR
PS3000RT3120XRW
Power Rating, VA/W
1000VA/900W
1500VA/1350W
1920VA/1920W
*
3000VA/2700W
Dimensions, W x D x H, in (mm)
Unit
17.3 x 19.3 x 3.5 (440 x 490.5 x 88)
17.3 x 27.6 x 3.5 (440 x 700.5 x 88)
Shipping
22 x 24.1 x 9 (560 x 612 x 228)
22 x 34.8 x 9.0 (560 x 884 x 228)
Weight, lb (kg)
Unit
56 (25)
62 (28)
92 (42)
105 (48)
Shipping
64 (29)
70 (32)
101 (46)
115 (52)
Input AC Parameters
Surge Protection
570J
Voltage Range
Without Battery Operation
83-159 VAC (configurable)
Frequency Range
45~65Hz, (±0.5Hz) 
Input Power Cord,
10ft (3m) attached
NEMA 5-15P plug
NEMA 5-20P plug
NEMA L5-30P plug
Output Receptacles
(6) NEMA 5-15R
(4) NEMA 5-15R
(2) NEMA 5-20R T-Slot,
accepts15A Plug
(4) NEMA 5-15R 
(2) NEMA 5-20R T-Slot,
accepts15A Plug
(1) NEMA L5-30R
Voltage (Normal Mode)
110/120/127 VAC (configurable)
Voltage (Battery Mode)
110/120/127 VAC; ±5% before low-battery warning
Transfer Time
4-6 ms typical
Waveform
 Sinewave
Battery Parameters
Type
Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Ah
4 x 12 x 7.2
 4 x 12 x 9
8 x 12 x 7.2
8 x 12 x 9
Recharge Time
5 hours to 90% of rated capacity, after full discharge into resistive load
Battery Backup Time
Full Load
5 minutes
Half Load
10 minutes
Environmental
Operating Temperature, °F (°C)
32 to 104 (0 to 40)
Storage Temperature, °F (°C)
5 to 104 (-15 to 40)
Relative Humidity
0% to 90%, non-condensing
Operating Altitude
Up to 10,000 ft (3000m)
Audible Noise
<45 dBA
Agency
Safety
UL 1778, c-UL Listed
Surge
ANSI C62.41 CatA Lev3 (surges) IEC61000-4-5
ESD
IEC61000-4-2
Susceptibility
IEC61000-4-3
Electrical Fast Transient
IEC61000-4-4
Emissions
FCC Part 15, Class A
Conducted Immunity
IEC61000-4-6
Harmonics
IEC61000-3-2
Network surge
UL 497 B
Transportation
ISTA Procedure 1A Certification
Environmental
ROHS compliant
*
NEC limits the input current rating of the PS2200RT3-120XR and PS2200RT3120XRW models to 80% of the input plug's rating. Up to 
2200VA/1980W is available by contacting a certified electrician to change the input plug to 30A plug. Emerson Network Power assumes no 
liability for damage caused by miswiring or misapplication of the input plug.