GE 1000 VA 用户手册

下载
页码 10
 
OPM_MLE_LTE_350_1K0_1GB_V011
 
5
 
DE ML Series: user manual 1.1 (GB)
 
GE Digital Energy
 ML Series
g
 
 
 
3.3  Use: Status and Alarm Indications 
 
o  status indications 
the operating mode 
 
!  low priority alarms 
abnormal operating situations 
 
!!  high priority alarms 
situations  in  which  the actual output voltage of the UPS is no longer 
guaranteed; immediate action should be taken 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
SITUATION LINE 
BAT 
BUZZER 
RESET 
BUZZER 
O 
Charger on 
(3.3.1) 
Mains on. 
UPS output off  
Green blinking 
1x /sec 
 
 
 
Normal 
operation 
(3.3.2) 
Mains on. 
UPS output on  
Green on 
 
 
 
 
On battery 
(3.3.3) 
Mains off or abnormal, UPS 
output on 
 
Red on 
Beeps 
1x /4 sec 
Possible* 
!! 
Battery low 
(3.3.4) 
UPS on battery, battery 
under drained condition 
 
Red on 
Beeps 
1x /sec 
Not 
possible 
Replace 
battery 
(3.3.5) 
Mains on, UPS output on. 
UPS has failed to pass the 
previous self test 
Green on 
(mains mode) 
Green blinking 
1x /sec 
(standby mode) 
Red 
blinking 
1x /30 sec 
Beeps 
1x /30 sec 
 
!! 
Overload on 
mains 
(3.3.6) 
Mains on, output power > 
105% of the rated capacity. 
Green on 
 
Continuous 
Not 
possible 
!! 
Overload on 
battery 
(3.3.6) 
Mains off or abnormal, 
Output power > 105% of the 
rated capacity. 
 Red 
on 
Continuous 
Not 
possible 
Self test 
(3.3.7) 
Mains on, unit switches to 
battery mode for 6 secs to 
check the bat. condition 
Green on 
Red on 
 
 
 
Operating modes and corresponding indications, see 3.3.1 – 3.3.7. 
 
 
Reset Buzzer alarm:  Press keypad  ‘ON’ for 2 seconds. 
 
Only the actual buzzer is muted; a next alarm re-activates the buzzer. 
 
A buzzer reset does not affect the computer interface alarm. 
 
 
3.3.1 Charger 
on 
Mains on, UPS output off, the batteries are charging. 
 
3.3.2 Normal 
operation 
Mains on, UPS output on, see also 3.2.1.